| Supply system | single-phase AC or DC |
| Input voltage AC | rated 120 to 230 V, range 93 to 264 V |
| Input voltage DC | 110 to 350 V |
| Line frequency | 50/60 Hz (47 to 63 Hz) |
| Wide-range input | yes |
| Input overvoltage withstand | 2.3 × rated input voltage for 1.3 ms |
| Mains buffering at rated current | min. 20 ms at 93/187 V input voltage |
| Input current | 2.5 A at 120 V, 1.3 A at 230 V |
| Inrush current limiting at 25 °C | max. 20 A, duration max. 3 ms |
| I²t value | max. 1.5 A²s |
| Input fuse | T 6.3 A (not accessible) |
| Protection of the mains feeder | miniature circuit breaker from 16 A, characteristic C (recommended) |
| Output voltage | 24 V DC, regulated, isolated, not adjustable |
| Overall tolerance of the output voltage | 1% |
| Static line regulation | 0.1% |
| Static load regulation | 0.2% |
| Dynamic line regulation | typ. 0.3% for a line step of ±15% |
| Dynamic load regulation | typ. 1.5% for a load step of 50/100/50%, settling time typ. 10 ms |
| Residual ripple | max. 100 mV |
| Voltage spikes | max. 100 mV |
| Switch-on behavior | no overshoot of the output voltage (soft start), start-up delay max. 3 s, voltage rise time typ. 100 ms |
| Indicator | green LED for 24 V OK |
| Output current | 10 A (range 0 to 10 A) |
| Active power output | typ. 240 W |
| Overload current on short circuit | typ. 11 A during start-up and in operation |
| Parallel connection for increased power | yes, 2 units |
| Efficiency | 85% |
| Power loss | typ. 42 W at rated load |
| Overvoltage protection | yes, according to EN 60950 |
| Short-circuit protection | short-circuit proof, constant current characteristic, current limiting response value 11 to 13 A |
| Continuous short-circuit current (RMS) | max. 14 A |
| Electrical isolation | yes, output voltage as safety extra-low voltage (SELV) according to EN 60950-1 |
| Protection class | I |
| Leakage current | max. 3.5 mA |
| Degree of protection | IP20 |
| Electromagnetic compatibility | emission EN 55022 class B, mains harmonics EN 61000-3-2, immunity EN 61000-6-2 |
| Approvals | CE, cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289, EAC |
| Approvals for hazardous areas and shipbuilding | none (IECEx, ATEX, UL Hazloc, FM, shipbuilding no) |
| MTBF at 40 °C | 1 250 000 h |
| Cooling | natural convection |
| Climate class to IEC 60721 | 3K3, 5 to 95% without condensation |
| Input connection | screw terminals L, N, PE, 1 terminal each for 0.5 to 2.5 mm² solid or finely stranded |
| Output connection | screw terminals L+ and M, 3 terminals each for 0.5 to 2.5 mm² |
| Design | S7-300 design |
| Dimensions (W × H × D) | 200 × 125 × 135 mm |
| Installation width × mounting height | 200 mm × 325 mm |
| Minimum clearances | top 100 mm, bottom 100 mm, left and right 0 mm |
| Mounting | DIN rail EN 60715 35x15 or S7 mounting rail, no wall mounting, can be lined up |
| Weight | 1.8 kg |