SM 431 analog input module with eight inputs, electrically isolated from the backplane bus, and a resolution of 14 bit, 16 bit with smoothing. It measures voltage, current, resistance, thermocouples and resistance thermometers such as Pt 100, with four channels available for resistance measurement.
General
| Manufacturer | Siemens |
| Type / model | SM 431 8 AI |
| Article number | 6ES7431-1KF10-0AB0 |
| Order number | 6ES7431-1KF10-0AB0 |
| Series | SIMATIC S7-400 |
| Condition | Used |
Technical data
| Load voltage | 24 V DC, only for supplying 2-wire transmitters, reverse polarity protected |
| Current consumption | max. 200 mA from L+ with 8 fully driven 2-wire transmitters, max. 600 mA from the backplane bus (5 V DC) |
| Power loss | typ. 3.5 W |
| Analog inputs | 8 for voltage and current, 4 for resistance measurement |
| Resolution | 14 bit including sign, 16 bit with smoothing |
| Voltage ranges | ±80 mV, ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V, 1 to 5 V |
| Current ranges | 0 to 20 mA, 4 to 20 mA |
| Thermocouples | type B, E, J, K, L, N, R, S, T, U |
| Resistance thermometers | Pt 100, Pt 200, Pt 500, Pt 1000, Pt 10000, Ni 100, Ni 1000 |
| Resistance ranges | 0 to 48 Ω, 0 to 150 Ω, 0 to 300 Ω, 0 to 600 Ω, 0 to 6000 Ω (usable up to 5000 Ω) |
| Input resistance | 1 MΩ for voltage, 50 Ω for current |
| Basic conversion time | 20.1 / 23.5 ms |
| Integration time | 16.7 / 20 ms, configurable |
| Interference frequency suppression | 50 / 60 Hz |
| Temperature compensation | external with Pt 100 or compensating box, no internal |
| Cable length | max. 200 m shielded, 50 m with thermocouples and ranges up to 80 mV |
| Operational error limit | voltage ±0.35 % (±0.38 % at ±80 mV), current ±0.35 %, resistance ±0.5 % |
| Basic error limit | voltage and current ±0.15 % at 25 °C |
| Electrical isolation | channels to backplane bus and load voltage, not between channels |
| Diagnostic function | no |
| Dimensions (W × H × D) | 25 × 290 × 210 mm |
| Weight | approx. 500 g |