| Number of analog inputs | 8, 4 for resistance measurement |
| Resolution | unipolar 9/12/12/14 bit, bipolar 9/12/12/14 bit + sign, max. 15 bit incl. sign |
| Integration time | 2.5 / 16.67 / 20 / 100 ms, parameterizable |
| Basic conversion time | 3 / 17 / 22 / 102 ms |
| Interference frequency suppression | 400 / 60 / 50 / 10 Hz |
| Voltage ranges | ±80 mV, ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V, 1 to 5 V |
| Current ranges | 0 to 20 mA, 4 to 20 mA, ±3.2 mA, ±10 mA, ±20 mA |
| Thermocouples | type E, J, K, L, N |
| Resistance thermometers | Pt100 and Ni100, standard and climatic range |
| Resistance ranges | 0 to 150 Ω, 0 to 300 Ω, 0 to 600 Ω |
| Input resistance | 10 MΩ for ±80 mV to ±1 V, thermocouples, resistance thermometers and resistors, 100 kΩ for ±2.5 V to ±10 V and 1 to 5 V, 25 Ω for current |
| Basic error limit at 25 °C | voltage ±0.6 %, current ±0.5 %, resistance ±0.5 %, resistance thermometer ±0.6 %, thermocouple ±0.7 %, relative to input range |
| Operational error limit | voltage ±1 %, current ±0.7 %, resistance ±0.7 %, resistance thermometer ±0.7 %, thermocouple ±1.1 %, over the entire temperature range |
| Alarms and diagnostics | diagnostic alarm parameterizable, limit value alarm parameterizable for channels 0 and 2, group error LED SF |
| Electrical isolation | channels to backplane bus and electronics supply yes, between channels no, test voltage 500 V DC |
| Load voltage L+ | 24 V DC, reverse polarity protected |
| Current consumption from L+ | max. 30 mA without load |
| Current consumption from backplane bus 5 V DC | max. 50 mA |
| Power loss | typ. 1 W |
| Shielded cable length | max. 200 m, 50 m for 80 mV and thermocouples |
| Front connector | 20-pin required |
| Dimensions (W × H × D) | 40 × 125 × 117 mm |
| Weight | approx. 250 g |