| Product version according to data sheet | hardware version 03, firmware V3.0 |
| Supply voltage | 24 V DC (20.4 to 28.8 V) |
| Current consumption in no-load operation | typ. 1.2 A |
| Inrush current | typ. 8 A |
| External protection (recommendation) | miniature circuit breaker 2 A, type B or C |
| Power loss | typ. 12 W |
| Work memory | 512 KByte (256 KByte code, 256 KByte data) |
| Load memory | 64 KByte RAM integrated, expandable with FEPROM up to 4 MByte or RAM up to 2 MByte |
| Backup | with battery all blocks, without battery 11 KByte |
| Processing times | typ. 0.1 µs bit, word and fixed point, 0.6 µs floating point |
| Blocks | max. 2047 DBs, 1024 FBs and 1024 FCs, max. 64 KByte each |
| Counters and timers | 512 S7 counters and 512 S7 timers, IEC counters and timers as SFB |
| Flags | 1024 bytes, retentivity adjustable from MB 0 to MB 1023 |
| Local data | max. 8192 bytes adjustable, preset 3584 bytes |
| I/O address area | 8 KByte each for inputs and outputs, process image 2048 bytes each (preset 256 bytes) |
| Digital channels | 65,536 inputs and 65,536 outputs, of which 1024 each central |
| Analog channels | 4096 inputs and 4096 outputs, of which 256 inputs and 128 outputs central |
| Configuration | max. 4 racks with max. 8 modules each, max. 3 expansion units |
| 1st interface | RS 485, isolated, MPI and PROFIBUS DP master or slave, max. 12 Mbit/s |
| 2nd interface | RS 485, isolated, PROFIBUS DP master or slave, max. 12 Mbit/s, max. 125 DP slaves |
| Direct data exchange | yes, as transmitter and receiver |
| Number of connections | 32 |
| Operating hours counters | 8, 0 to 32767 hours each |
| Clock | hardware clock, deviation max. 10 s per day |
| Diagnostic buffer | 100 entries |
| GSD file | siem807f.gsg |
| Dimensions (W × H × D) | 160 × 125 × 130 mm |
| Weight | approx. 930 g |