| Product version according to data sheet | functional status 01, firmware V3.3 |
| Supply voltage | 24 V DC (19.2 to 28.8 V) |
| External protection (recommendation) | miniature circuit breaker type C min. 2 A or type B min. 4 A |
| Mains buffering | 5 ms, repeat rate min. 1 s |
| Load voltage L+ | 24 V DC, digital inputs with reverse polarity protection, digital outputs without |
| Current consumption | 650 mA rated value, typ. 150 mA at no load, inrush current typ. 5 A (I²t 0.7 A²s) |
| Current consumption from load voltage L+ | digital inputs max. 80 mA without load, digital outputs max. 50 mA |
| Power loss | typ. 12 W |
| Work memory | 128 KByte, integrated, not expandable |
| Load memory | plug-in Micro Memory Card, max. 8 MByte, data retention min. 10 years after the last programming |
| Backup | maintenance-free via the Micro Memory Card, program and data without battery |
| Processing times | typ. 0.07 µs per bit operation, 0.15 µs per word operation, 0.2 µs fixed-point arithmetic, 0.72 µs floating-point arithmetic |
| Blocks | total 1024 DBs, FBs and FCs, max. 64 KByte each, DB numbers 1 to 16000, FB and FC numbers 0 to 7999 |
| Nesting depth | 16 per priority class, additional 4 within an error OB |
| Counters and timers | 256 S7 counters (0 to 999) and 256 S7 timers (10 ms to 9990 s), IEC counters and timers as SFB |
| Flags | 256 bytes, retentivity adjustable MB 0 to MB 255 (default MB 0 to MB 15), 8 clock memory bits |
| Retentive data area | max. 64 KByte (incl. timers, counters and flags) |
| Local data | max. 32 KByte per priority class, max. 2048 bytes per block |
| I/O address area | 1024 bytes each for inputs and outputs, process image adjustable up to 1024 bytes (default 128 bytes) |
| Digital channels | 1016 inputs and 1008 outputs, all central |
| Analog channels | 253 inputs and 250 outputs, all central |
| Configuration | max. 4 racks with 8 modules each (max. 7 in rack 3), max. 3 expansion units, up to 4 DP masters via CP, recommended up to 8 FM, 8 CP PtP and 6 CP LAN |
| Clock | hardware clock, retentive and synchronizable, backup time 6 weeks at 40 °C, deviation max. 10 s per day (typ. 2 s) |
| Digital inputs | 24 × 24 V DC, of which 12 for technological functions, characteristic to IEC 61131 type 1 |
| Input voltage | signal 0 −3 to +5 V, signal 1 +15 to +30 V |
| Input current for signal 1 | typ. 8 mA |
| Input delay | 0.1 / 0.3 / 3 / 15 ms parameterizable (rated value 3 ms), max. 16 µs for technological functions |
| Digital outputs | 16 × 24 V DC, of which 4 high-speed outputs, short-circuit proof (electronically clocked, response threshold typ. 1 A) |
| Output current | rated value 500 mA for signal 1, permissible 5 mA to 0.6 A, residual current for signal 0 max. 0.5 mA |
| Switching frequency | max. 100 Hz with resistive load and lamp load, max. 0.5 Hz with inductive load, pulse outputs max. 2.5 kHz |
| Lamp load | max. 5 W |
| Total current of the outputs | per group max. 3 A up to 40 °C and max. 2 A up to 60 °C with horizontal installation, max. 2 A up to 40 °C with vertical installation |
| Analog inputs | 4 for current or voltage and 1 for resistance or Pt 100 |
| Input ranges (input resistance) | ±10 V and 0 to 10 V (100 kΩ), ±20 mA, 0 to 20 mA and 4 to 20 mA (100 Ω), Pt 100 and 0 to 600 Ω (10 MΩ) |
| Analog outputs | 2, voltage 0 to 10 V and ±10 V, current 0 to 20 mA, ±20 mA and 4 to 20 mA |
| Load impedance of analog outputs | voltage output min. 1 kΩ (capacitive max. 0.1 µF), current output max. 300 Ω (inductive max. 0.1 mH) |
| Resolution of analog values | 12 bits incl. sign for inputs and outputs |
| Measuring principle of analog inputs | actual value encoding (successive approximation), integration time 16.6 or 20 ms, interference frequency suppression 50/60 Hz |
| Integrated functions | 3 counters up to 30 kHz, frequency measurement with 3 channels up to 30 kHz, 3 pulse outputs with pulse width modulation up to 2.5 kHz, PID controller |
| MPI interface | RS 485, non-isolated, max. 187.5 kbit/s, 8 connections |
| Diagnostic buffer | 500 entries, of which 100 retained on power failure |
| Electrical isolation | digital inputs to backplane bus, digital outputs in groups of 8 and to backplane bus, analog section jointly to backplane bus |
| Isolation tested with | 600 V DC |
| Operating ambient temperature | 0 to 60 °C |
| Front connector | 2 × 40-pin, required |
| Configuration software | STEP 7 V5.5 SP1 or higher, or V5.3 SP2 or higher with HSP 203 |
| Programming languages | LAD, FBD, STL, SCL, CFC, GRAPH, HiGraph |
| Dimensions (W × H × D) | 120 × 125 × 130 mm |
| Weight | approx. 660 g |