| Product version according to manual | hardware 01, firmware V1.1.0 |
| Supply voltage | 24 V DC (20.4 to 28.8 V) |
| Current consumption in no-load operation | typ. 0.7 A |
| Inrush current | typ. 8 A |
| External protection (recommendation) | miniature circuit breaker 10 A, type B or C |
| Power loss | typ. 9 W |
| Work memory | 6 KByte, not expandable |
| Load memory | 20 KByte RAM and 20 KByte EEPROM integrated, not expandable |
| Retentivity without battery | 72 bytes, configurable for data, flags and timers |
| Processing times | min. 0.6 µs bit, 2 µs word, 3 µs fixed point, 60 µs floating point |
| Blocks | max. 32 FBs, 32 FCs and 63 DBs, max. 6 KByte each |
| Counters and timers | 32 S7 counters, 64 S7 timers, IEC counters and timers as SFB |
| Flags | 1024, retentivity adjustable from MB 0 to MB 71 |
| Integrated inputs and outputs | 10 digital inputs, up to 4 of them as special inputs, and 6 digital outputs |
| Digital inputs | 24 V DC, signal 1 at 11 to 30 V, typ. 7 mA, delay 1.2 to 4.8 ms, IEC 1131 type 2 |
| Special inputs | 4 (I 124.6 to I 125.1), process alarm configurable, input frequency up to 10 kHz |
| Digital outputs | 6, rated current 0.5 A (5 mA to 0.6 A), electronic clocked short-circuit protection, total current max. 3 A |
| Switching frequency of outputs | max. 100 Hz with resistive and lamp load, max. 0.5 Hz with inductive load |
| Integrated functions | 1 counter, frequency meter up to max. 10 kHz |
| Front connector | 20-pin for the integrated inputs and outputs |
| MPI interface | non-isolated, 19.2 and 187.5 kbaud |
| Connection resources | 6 for PG, OP, S7 basic and S7 communication |
| Clock | yes, not backed up |
| Diagnostic buffer | 100 entries |
| Dimensions (W × H × D) | 80 × 125 × 130 mm |
| Weight | approx. 0.45 kg |