| Units according to manufacturer | Central controller 150U (AG S5-150U) |
| Rated input voltage | 110 or 220 V AC ±15%, switchable via voltage selector |
| Input undervoltage signal | at ≤ 187 V |
| Input frequency | 50 Hz |
| Input current at rated load | 2.95 A at 220 V, 5.9 A at 110 V |
| Peak inrush current | 200 A at 220 V, 100 A at 110 V |
| Efficiency at rated load | 79% without fan, 65% with fan |
| Hold-up time on mains failure | typ. 15 ms |
| Power factor | 0.73 |
| Input fuse | 6 A fast-acting, 250 V, 6.3 × 32 mm |
| Output 1 | 5.1 V DC ±0.5%, 40 A |
| Ripple of output 1 | ≤ 1% |
| Dynamic voltage tolerance of output 1 | ≤ 5% for a load step from 50% to 100%, settling time ≤ 5 ms |
| Overvoltage shutdown of output 1 | at 6 V ±5% |
| Current limiting of output 1 | between 1.05 and 1.15 × rated current |
| Output 2 | 24 V DC +25%/-17%, 2.8 A |
| Fuse of output 2 | 4 A fast-acting, 250 V, 6.3 × 32 mm |
| Output 3 | 15 V DC ±5%, 2 A, only with retrofitted add-on module |
| Current limiting of output 3 | ≥ 2 A |
| Overvoltage protection of output 3 | ≥ 18.5 V |
| Undervoltage signal of output 3 | at 14 V ±3% (green LED on the front panel) |
| Total current of outputs 2 and 3 | ≤ 2.8 A |
| Output 4 | not available, only version -3LF12 has the 24 V front output |
| Fans | 2 axial fans, 230/115 V AC, switchable |
| Air flow per fan | 160 m³/h (no-load value, data sheet value) |
| Fan monitoring | air flow monitoring with PTC thermistors, fan standstill is output as a signal via LED and relay or switches off the output voltage depending on the jumper setting |
| Power loss | max. 140 W |
| 15 V add-on module according to spare parts list | 6ES5956-0AA11 |