| Construction | processor with floating-point coprocessor, bus controller for communication via the backplane bus, microcontroller for the interfaces |
| Total memory capacity | max. 256 KByte |
| Internal program memory | max. 256 KByte RAM |
| Memory card | flash EPROM 128, 256 or 512 KByte, of which max. 256 KByte usable |
| Execution time per operation | approx. 0.1 to 1.35 µs |
| Floating-point arithmetic | addition, subtraction and multiplication 0.75 µs, division 1.35 µs |
| Interrupt response time | typ. 50 µs |
| Integrated clock | accuracy ±2 s/day, approx. 0 to −4 s/day at 40 °C |
| Scan time monitoring | approx. 500 ms (adjustable) |
| Flags | 2048, optionally half or all retentive |
| S flags | 32768, optionally half or all retentive |
| Timers | 256, optionally half or timers 0 to 63 retentive, time range 0.01 to 9990 s |
| Counters | 256, optionally half or counters 0 to 63 retentive, counting range 0 to 999 (up, down) |
| Digital inputs and outputs | max. 8192 in total, of which 1024 inputs and 1024 outputs with process image |
| Analog inputs and outputs | max. 256 in total |
| Blocks | max. 256 each of OB, PB and SB, max. 512 FB/FX (parameterizable), max. 512 DB/DX |
| Block nesting depth | max. 50 |
| Operation set | approx. 270 operations |
| Programming languages | STEP 5, SCL |
| Serial interfaces | SI 1 built in for PG, OP 393 or SINEC L1, SI 2 as receptacle for an interface module (PG, TTY, V.24, RS 422A/485 or SINEC L1) |
| Controls | STOP/RUN mode selector, switch for retentivity preset (NR, RE) and overall reset (OR) |
| Indicators | RUN and STOP LEDs, fault indicators QVZ, ZYK and BASP |
| Backup current at power off | internal RAM approx. 100 µA |
| Current consumption from 5 V | typ. 0.5 A without interface module |
| Current consumption from 24 V | 0.06 A |
| Power loss | typ. 4.2 W without interface module |
| Weight | approx. 0.8 kg |