| Number of inputs | 16 for voltage or current, or 8 for Pt 100 |
| Electrical isolation | no, non-isolated |
| Measuring ranges | ±50 mV, ±500 mV, Pt 100, ±1 V, ±5 V, ±10 V, ±20 mA, 4 to 20 mA |
| Range selection | per group of four channels via plug-in range cards 6ES5 498-1AA11 to -1AA71 |
| Input resistance | 10 MΩ at ±50 mV, ±500 mV and Pt 100, 90 kΩ at ±1 V, 50 kΩ at ±5 V and ±10 V, 25 Ω at ±20 mA, 31.25 Ω at 4 to 20 mA |
| Sensor connection | two-wire connection, four-wire connection for Pt 100 |
| Measured value representation | 12 bits plus sign or 13 bits two's complement, 2048 units correspond to the rated value |
| Measuring principle | integrating, voltage-time conversion (dual slope) |
| Integration time | 20 ms at 50 Hz, 16.6 ms at 60 Hz |
| Coding time per measured value | max. 60 ms at 50 Hz, max. 50 ms at 60 Hz |
| Coding time for all inputs | 0.48 s with 8 and 0.96 s with 16 inputs (50 Hz) |
| Noise suppression | common mode min. 86 dB, series mode min. 40 dB at f = n × (50/60 Hz ±1%) |
| Basic error limits | ±2 ‰ (±50 mV), ±1.5 ‰ (±500 mV), ±2 ‰ (Pt 100), ±3.5 ‰ (±1 V, ±5 V, ±10 V), ±2.5 ‰ (±20 mA, 4 to 20 mA) |
| Operational error limits | at 0 to 55 °C ±5 ‰ (±50 mV), ±4.5 ‰ (±500 mV), ±5 ‰ (Pt 100), ±7.7 ‰ (±1 V, ±5 V, ±10 V), ±6.7 ‰ (±20 mA, 4 to 20 mA) |
| Overrange indication | yes, above 4095 units |
| Wire break signal | configurable for the 50 mV and 500 mV (Pt 100) ranges, test current can be switched off |
| Permissible voltage between inputs | max. 18 V, 75 V for max. 1 ms at a duty cycle of 1 to 20 (destruction limit, also to the central grounding point) |
| Shielded cable length | max. 200 m, max. 50 m for ±50 mV |
| Front connector | 46-pin |
| Supply voltage | 24 V DC (20 to 30 V), only for two-wire transducers or for disconnecting the wire break test current |
| Current consumption from 5 V internal | typ. 0.15 A |
| Current consumption from 24 V | max. 20 mA per transducer |
| Power loss | typ. 0.75 W |
| Settings on the rear | function selector switches for reference junction compensation, 50 or 500 mV range, 8 or 16 channels, cyclic or selective sampling, 50 or 60 Hz, value representation and wire break signal |
| Weight | approx. 0.4 kg |