| Digital inputs | 8, fail-safe, sourcing (P-reading), characteristic to IEC 61131 type 1 |
| Achievable safety class | SIL 3 to IEC 61508, PL e to ISO 13849-1 |
| Probability of failure | PFDavg < 2.00E-05, PFH < 1.00E-09 1/h (20 years service life, 100 h repair time) |
| Input voltage | 24 V DC, signal 0 at -30 to +5 V, signal 1 at +15 to +30 V |
| Input current at signal 1 | typ. 3.7 mA |
| Input delay | parameterizable, 0.4 to 20 ms |
| Sensor supply | 8 outputs, max. 0.3 A each up to 60 °C, max. 800 mA in total, min. L+ minus 1.5 V, short-circuit proof (response threshold 0.7 to 1.8 A) |
| Supply voltage | 24 V DC (20.4 to 28.8 V), reverse polarity protected |
| Current consumption | 75 mA without load |
| Current consumption from the backplane bus | max. 21 mA |
| Power consumption from the backplane bus | 70 mW |
| Power loss | typ. 4 W |
| Address space | 6 bytes of inputs, 4 bytes of outputs |
| Matching base unit | BaseUnit type A0 |
| Coding | automatic, electronic coding element type F |
| Cable length | shielded max. 1000 m, unshielded max. 500 m |
| Interrupts | diagnostic interrupt yes, hardware interrupt no |
| Indicators | LED RUN green, ERROR red, PWR green, channel status green, channel diagnostics red, DIAG green/red |
| Electrical isolation | between channels no, channels to backplane bus yes, channels to electronics supply no |
| Isolation tested with | 707 V DC (type test) |
| Configuration | STEP 7 TIA Portal V12 or later, STEP 7 V5.5 SP3 or later, PROFINET GSD V2.31 or later |
| I&M data | I&M0 to I&M3 |
| Reparameterization in RUN | not possible |
| Operating ambient temperature | 0 to 60 °C horizontal, 0 to 50 °C vertical |
| Operating altitude | max. 4000 m above sea level, restrictions above 2000 m |
| Dimensions (W × H × D) | 15 × 73 × 58 mm |
| Weight | approx. 49 g |