| Digital inputs | 16, not isolated from each other, isolated from the backplane bus |
| Input voltage | 24 V DC (rated value), signal 0 at -30 to +5 V |
| Input current at signal 1 | typ. 3 mA at 24 V |
| Input delay | typ. 3 ms (1.2 to 4.8 ms) |
| Input characteristic | to IEC 61131 type 1 |
| Connection of two-wire sensors | possible, quiescent current max. 1.5 mA |
| Sensor supply | 500 mA, electronically short-circuit proof per voltage group, min. L+ minus 0.5 V |
| Digital outputs | 16, transistor, isolated in groups of up to 8 |
| Output current at signal 1 | 0.5 A rated, permissible 7 mA to 0.6 A |
| Output voltage | signal 1 min. L+ minus 0.8 V |
| Residual current at signal 0 | max. 0.5 mA |
| Total current of outputs | per voltage group horizontal max. 4 A up to 30 °C, 3 A up to 40 °C, 2 A up to 60 °C, vertical max. 2 A up to 55 °C |
| Load resistance | 48 Ω to 4 kΩ |
| Lamp load | max. 5 W |
| Switching frequency | max. 100 Hz resistive, 2 Hz inductive, 10 Hz lamp load |
| Output delay | 0 to 1 max. 0.5 ms, 1 to 0 max. 1.3 ms |
| Short-circuit protection | yes, per channel, response threshold 0.7 to 1.9 A |
| Limitation of inductive shutdown voltage | typ. L+ minus 55 to 60 V |
| Controlling a digital input | possible |
| Fieldbus | PROFIBUS DP, RS 485, DPV0 slave, SYNC, FREEZE and direct data exchange |
| Transmission rates | 9.6, 19.2, 45.45, 93.75, 187.5 and 500 kBaud and 1.5, 3, 6 and 12 Mbit/s |
| Isochronous mode | no |
| Expansion | up to 12 ET 200S modules, no F modules, current carrying capacity for connected modules max. 5 A |
| Address space | interface module 100 bytes of inputs and 100 bytes of outputs, integrated I/O 2 bytes of inputs and 2 bytes of outputs |
| Manufacturer ID | 8200H |
| Supply voltage | 24 V DC at 1L+, reverse polarity protected, no power failure buffering |
| Current consumption | max. 100 mA from 1L+ |
| Output current of the PROFIBUS interface | max. 80 mA |
| Interrupts | none |
| Diagnostics | short circuit of sensor supply, missing load voltage, module-granular |
| Indicators | LED SF and BF red, ON green, status per channel green |
| Electrical isolation | PROFIBUS DP to electronics yes, backplane bus and supply to electronics no |
| Isolation tested with | 500 V DC |
| Permissible potential difference | 75 V DC / 60 V AC |
| Matching terminal modules | TM-C120C with spring terminals, TM-C120S with screw terminals |
| Power loss | typ. 3 W |
| Dimensions (W × H × D) | 120 × 81 × 58 mm |
| Weight | approx. 230 g without terminal module |