| Function | Temperature converter with trip values, isolated barrier (intrinsically safe) |
| Channels | 1 |
| Supply | 20 to 30 V DC (terminals 23/24 or Power Rail), approx. 100 mA |
| Power dissipation / consumption | max. 2 W / 2.2 W |
| RTD input | Pt100, Pt500, Pt1000, Ni100, Ni1000, 2-, 3- or 4-wire |
| Thermocouple input | Types B, E, J, K, L, N, R, S, T, redundant second sensor possible |
| Cold junction compensation | external or internal (with terminal block K-CJC-**) |
| Potentiometer input | 0.8 to 20 kΩ, 2-, 3- or 5-wire |
| Voltage input | 0 to 10 V, 2 to 10 V, 0 to 1 V, −100 to 100 mV |
| Current output | 0/4 to 20 mA, load max. 650 Ω, fault signal per NE43 |
| Relay outputs | 2 relays, 250 V AC / 2 A, 40 V DC / 2 A |
| Accuracy | RTD max. 0.2 % of span, thermocouple max. 10 µV, voltage 0.1 % of span |
| Sampling rate | approx. 700 ms |
| Operation | LC display, keys, PACTware via RS232 socket |
| Galvanic isolation | reinforced insulation per EN 61010-1, 300 V rms |
| Functional safety | up to SIL 2 (IEC 61508 / IEC 61511) |
| Ex marking | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I |
| Certificates | TÜV 03 ATEX 2140, IECEx TUN 09.0019, Zone 2: PF 08 CERT 1213 X |
| Ambient temperature | −20 to 60 °C |
| Degree of protection | IP20 |
| Connection | removable screw terminals |
| Mounting | 35 mm DIN rail, Power Rail |
| Dimensions (W × H × D) | 40 × 119 × 115 mm |
| Weight | 300 g |