| Version | StateLine C (SC), built-in unit (E), standard ambient conditions (S), with safety engineering STO (B) |
| Typical motor power | 0.75 kW (4-pole asynchronous motor) |
| Voltage class | 400/500 V, 3/PE AC |
| Line voltage | 3/PE AC 320 V −0% to 550 V +0% |
| Line frequency | 45 Hz −0% to 65 Hz +0% |
| Alternative DC supply | DC 455 V −0% to 775 V +0% |
| Rated output current | 2.40 A |
| Overload capacity | 150% of the rated output current for 60 s, 200% for 3 s |
| Maximum motor cable length | 100 m unshielded, 50 m shielded (technically possible, irrespective of EMC requirements) |
| Control types | V/f control without encoder (linear or square-law), sensorless vector control (torque and speed), V/f control with encoder |
| Maximum output frequency | 1000 Hz |
| Fixed frequencies | 15 |
| Analog input | 1, optionally voltage or current, 10 bit, 0 to ±10 V or 0/4 to 20 mA |
| Analog output | 1, 10 bit, 0 to 10 V |
| Digital inputs | 5, PLC switching level to IEC 61131-2, max. 11 mA |
| Digital output | 1, PLC switching level to IEC 61131-2, max. 50 mA |
| Relay | 1 changeover contact, AC 250 V, 3 A, DC 24 V, 2 A to 240 V, 0.16 A |
| Encoder input | via 2 digital inputs, HTL, two-track, 10 kHz, can also be used as frequency input |
| External DC supply | 24 V for mains-independent supply of the control electronics |
| Fieldbus | CANopen integrated, functional insulation, max. 500 kbit/s, communication module optional |
| Safety engineering | Safe Torque Off (STO), certified to EN ISO 13849-1 (Cat. 4, PL e) and EN 61508/EN 62061 (SIL 3) |
| Braking operation | brake chopper integrated, brake resistor external |
| Monitoring and protective functions | short circuit, earth fault, overvoltage, motor stalling, I²t, motor phase failure, mains phase failure, protection against cyclic mains switching, motor overtemperature via PTC or thermal contact |
| Diagnostics | integrated interface for USB diagnostic adapter or X400 keypad, 4 status LEDs |
| Memory module | pluggable, stores all drive settings, fitted ex works |
| Degree of protection | IP20, NEMA 250 Type 1 |
| Operating ambient temperature | −10 to +55 °C (3K3), above 45 °C derating 2.5%/K |
| Storage and transport temperature | storage −25 to +60 °C (1K3), transport −25 to +70 °C (2K3) |
| Operating altitude | up to 4000 m above sea level, above 1000 m derating 5% per 1000 m |
| Marking and approval | CE according to Low Voltage Directive 2006/95/EC, UL 508C (file E132659) |
| Dimensions (W × H × D) | 70 × 215 × 199 mm, with safety engineering 20 mm more depth according to catalogue |
| Weight | 1.8 kg without communication module, version with safety engineering 0.1 kg more according to catalogue |